Not every accessible toilet is the same size. BS 8300-2:2018 sets out three main unisex accessible toilet layouts, and the right one depends on how many toilets your building has and who will use them. The smallest needs a room of at least 2200mm x 1700mm; the largest needs at least 2200mm x 2400mm.
"Doc M" is the shorthand most people use for accessible washrooms, after Approved Document M of the Building Regulations. BS 8300-2:2018 is the British Standard that gives the detailed layouts designers work from. Getting the room size right at the planning stage matters: once the walls are up, there is no easy way to find an extra 300mm.
Below, we walk through each of the three layouts, the minimum room size and where the key fittings go.
1. Unisex accessible toilet where other toilets are available
Minimum room size: 2200mm deep x 1700mm wide (BS 8300-2:2018, Fig 40)
This is the most common layout, used in Offices, Shops, Restaurants and other buildings where standard toilets are also provided. Because people have other options, the room can be the most compact of the three.
The toilet sits against the back wall, close to one side wall, so the user can use a wall-mounted grab rail on one side and a hinged drop-down rail on the other. A clear turning space is kept in front of the toilet so a wheelchair user can turn and transfer.


| Fitting | Dimension |
|---|---|
| Back wall to front of toilet pan | 750mm |
| Side wall to toilet centreline | 500mm |
| Toilet centreline to hinged grab rail | 320mm |
| Side wall to outer edge of fittings | 970mm |
2. Unisex accessible toilet with corner toilet, where it is the only toilet in the building
Minimum room size: 2200mm x 2000mm (BS 8300-2:2018, Fig 41)
Where only one toilet is provided in a building, it has to work for everyone, so the room is larger. The toilet sits in a corner, with a full-size washbasin on the opposite wall as well as a small hand-rinse basin within reach of the toilet.
The toilet centreline is set at least 1500mm from the opposite wall, which leaves the clear space needed for a wheelchair to approach and transfer. A 600mm grab rail runs along the side wall next to the toilet.


| Fitting | Dimension |
|---|---|
| Back wall to front of toilet pan | 750mm |
| Side wall to toilet centreline | 500mm |
| Toilet centreline to opposite wall | 1500mm min |
| Toilet centreline to hinged grab rail | 320mm |
| Side wall to outer edge of fittings | 970mm |
| Side-wall grab rail length | 600mm |
| Back wall to start of side-wall grab rail | 200–250mm |
| Front of toilet pan to hand-rinse basin | 140–160mm |
| Door-side wall to main basin centreline | 750mm |
3. Unisex accessible toilet with peninsular toilet for assisted use
Minimum room size: 2200mm wide x 2400mm deep (BS 8300-2:2018, Fig 45)
Some users need one or two carers to help them. A peninsular toilet layout brings the toilet out from the corner so there is open space on both sides, letting a carer assist from either side or a user transfer from the left or the right.
The toilet is set against the back wall with 1400mm to one side wall and 1000mm to the other. Hinged grab rails are fitted on both sides. This layout suits care homes, hospitals, day centres and other healthcare settings.


| Fitting | Dimension |
|---|---|
| Back wall to front of toilet pan | 750mm |
| Toilet centreline to wider side wall | 1400mm |
| Toilet centreline to narrower side wall | 1000mm |
| Toilet centreline to each hinged grab rail | 320mm |
| Grab rail to outer fitting (each side) | 150mm |
| Door-side wall to basin centreline | 750mm |
Which layout do you need?
The choice comes down to two questions: is this the only toilet in the building, and will users need help from a carer?
| Layout | When to use it | Minimum room size | BS 8300-2:2018 |
|---|---|---|---|
| Unisex accessible toilet | Other toilets are available in the building | 2200 x 1700mm | Fig 40 |
| Corner toilet, only toilet | It is the only toilet in the building | 2200 x 2000mm | Fig 41 |
| Peninsular toilet, assisted use | Users may need help from one or two carers | 2200 x 2400mm | Fig 45 |
Whatever the layout, three dimensions stay the same: the front of the toilet pan sits 750mm from the back wall, the hinged grab rail sits 320mm from the toilet centreline, and the washbasin centreline is 750mm from its wall.
Frequently asked questions
What is the minimum size for a Doc M accessible toilet?
Where other toilets are available in the building, a unisex accessible toilet needs a room of at least 2200mm deep x 1700mm wide (BS 8300-2:2018, Fig 40).
What size should an accessible toilet be if it is the only toilet in the building?
At least 2200mm x 2000mm, with a corner toilet, a full-size basin and a hand-rinse basin within reach of the toilet (BS 8300-2:2018, Fig 41).
What size is an accessible toilet for assisted use?
A peninsular layout for assisted use needs at least 2200mm x 2400mm, so carers can help from either side of the toilet (BS 8300-2:2018, Fig 45).
How far should the toilet pan project from the back wall?
In all three layouts, the front of the toilet pan sits 750mm from the back wall.
How far should the toilet be from the side wall?
In the corner layouts, the toilet centreline is 500mm from the side wall. The hinged grab rail is 320mm from the centreline, on the open side of the toilet.